Electrical Cable Sizing Guide: Professional Formulas, Load Tables & Real-World Examples

Learn professional electrical cable sizing with formulas, load tables, voltage drop checks, and real-world examples for safe, efficient designs.


Electrical cable sizing is one of the most essential and technically significant tasks in electrical design, yet it is often overlooked or simplified in real-world projects. Selecting the correct conductor affects not only the efficiency of an electrical system but also its long-term safety, reliability and cost. When a cable is improperly sized—whether too small or unnecessarily large—the consequences can include overheating, high energy losses, premature insulation failure, nuisance tripping, unexpected downtime and even fire hazards. 

Despite the availability of standards like IEC 60364, NEC and BS 7671, many engineers, technicians and installers continue to face challenges when applying these guidelines to practical, real-world scenarios. Factors such as ambient temperature, grouping, installation method, conductor material, load characteristics and voltage drop requirements must be evaluated holistically, not in isolation. 

This tutorial presents a complete, step-by-step methodology used by professional electrical engineers to determine the right cable size for any application—from residential lighting circuits to industrial motor feeders and long-distance infrastructure. It includes clear mathematical formulas, standard-based selection tables, realistic examples and answers to common field questions. Whether you are a practicing engineer, a new technician or a technical student, this guide will help you design safer, more efficient and fully compliant electrical installations with confidence.

1. Why Professional Cable Sizing Matters

Correct cable sizing ensures thermal stability, operational reliability and protection against electrical faults. An undersized cable overheats, degrades insulation and increases fire risks. An oversized cable wastes material and installation cost. Therefore, professional cable sizing follows a structured calculation process aligned with IEC 60364, NEC, BS 7671 and similar global standards.

2. Standard Engineering Workflow

Electrical design engineers use the following sequence:

  1. Determine design load current \( I_d \).
  2. Select preliminary cable size from standard tables.
  3. Apply correction (derating) factors.
  4. Verify voltage drop over actual running distance.
  5. Check short-circuit thermal withstand capacity.
  6. Finalize and document the selected conductor.

3. Step 1 — Determine Load Current

The foundation of cable sizing is computing the continuous load current. For single-phase systems:

\[ I_d = \frac{P}{V \cos\phi} \]

For three-phase systems:

\[ I_d = \frac{P}{\sqrt{3} \, V \cos\phi} \]

Where:

  • \( P \) = Active power (W)
  • \( V \) = RMS voltage (V)
  • \( \cos\phi \) = Power factor

Example: A 15 kW, 400 V, 3-phase motor with power factor 0.86:

\[ I_d = \frac{15000}{\sqrt{3} \times 400 \times 0.86} \approx 25.2\,A \]

4. Step 2 — Preliminary Cable Size Selection

Using current rating tables (IEC 60364-5-52 example), possible capacities for PVC-insulated copper conductors installed in conduit are:

Cable Size (mm²)Typical Ampacity (A)Application Examples
2.5 mm²18–25 ALighting, small motors
4 mm²25–32 AFeeders, pumps
6 mm²32–40 AAC compressors, industrial circuits
10 mm²45–63 ADistribution boards
16 mm²63–85 AMain feeders, industrial machinery

For our 25.2 A load current, 4 mm² or 6 mm² may be candidates — but the final choice depends on derating and voltage drop.

5. Step 3 — Applying Derating Factors

Cable ampacity is reduced by real-world conditions. The correction factor \( F \) is the product of all modifiers:

\[ F = F_{temp} \times F_{group} \times F_{ins} \times F_{method} \]

Typical Derating Values

ConditionDerating Factor
Ambient 45°C0.82
Grouping: 3 cables0.70
Thermal insulation0.80

Thus overall:

\[ F = 0.82 \times 0.70 = 0.574 \]

Required corrected ampacity:

\[ I_{req} = \frac{I_d}{F} = \frac{25.2}{0.574} \approx 43.9\,A \]

This eliminates 4 mm² and 6 mm² cables. The next size, 10 mm² (≈45–63 A), becomes compliant.

6. Step 4 — Voltage Drop Verification

Voltage drop must not exceed limits specified by national codes (often 3–5%). For three-phase systems:

\[ VD = \sqrt{3} \, I_d \, L \, (R \cos\phi + X \sin\phi) \]

The simplified method using mV/A/m values:

\[ VD = \frac{mV}{A\cdot m} \times I_d \times L \]

Example: For 10 mm² copper (approximately 4.4 mV/A/m) with a 70 m run:

\[ VD = 4.4 \times 25.2 \times 70 = 7766\,mV = 7.77\,V \]

Percentage drop:

\[ \%\;VD = \frac{7.77}{400} \times 100 \approx 1.94\% \]

This passes typical 3% feeder limits.

7. Step 5 — Short-Circuit Thermal Check

Cables must tolerate the fault energy for protection clearing time. The adiabatic equation is:

\[ S = \frac{I_{sc} \sqrt{t}}{k} \]

Where:

If calculated conductor size ≤ selected size, the cable passes thermal withstand requirements.

8. Real-World Industrial Example

Scenario: A wastewater plant needs to power a 22 kW pump located 120 m from the MCC. The environment reaches 48°C, and the cables run in a tray with seven other circuits.

Step 1: Load Current

\[ I_d = \frac{22000}{\sqrt{3} \times 400 \times 0.84} \approx 37.8\,A \]

Step 2: Preliminary Selection → 10 mm² or 16 mm².

Step 3: Derating:

  • Temperature at 48°C → \( F_{temp} = 0.76 \)
  • Grouping: 8 cables → \( F_{group} = 0.60 \)

\[ F = 0.76 \times 0.60 = 0.456 \]

\[ I_{req} = \frac{37.8}{0.456} \approx 82.9\,A \]

16 mm² copper (~85 A) becomes the only acceptable choice.

Step 4: Voltage Drop
16 mm² copper ≈ 2.8 mV/A/m.

\[ VD = 2.8 \times 37.8 \times 120 = 12614\,mV = 12.6\,V \]

% drop = 12.6 / 400 × 100 = 3.15% → acceptable.

Final Selection: 16 mm² Cu, 4C, XLPE insulated.

9. International Cable Size Guide (Quick Reference)

Load (A)IEC (Cu)NEC AWG (Cu)Typical Application
10–15 A1.5 mm²14 AWGLighting circuits
16–25 A2.5 mm²12 AWGSockets, appliances
25–35 A4 mm²10 AWGSmall motors, HVAC
40–55 A6 mm²8 AWGLarge appliances, feeders
60–85 A10–16 mm²6–4 AWGMain feeders, industrial motors
100–150 A25–35 mm²3–1 AWGDistribution panels

10. Frequently Asked Questions (FAQ)

1. Is voltage drop or ampacity more important?

Both are mandatory checks. For long distances, voltage drop is often the deciding factor, whereas in hot or crowded conditions, ampacity and derating dominate.

2. Should I always oversize cables for motors?

Not necessarily. Motors draw high starting current, but cables are sized for running current. Only in long distances or high thermal conditions should you consider the next size.

3. Do aluminum cables follow the same rules?

The methodology is identical, but aluminum has lower conductivity, so the required cross-section is larger. Mechanical strength and termination quality must also be checked.

4. Why do international standards differ?

Environmental assumptions, installation methods and safety margins vary by region. Always use the standard mandated by local regulation or project specifications.

5. How often should cable sizing be recalculated?

Whenever loads change, installation method changes, or environment conditions differ. Good engineering practice recommends reviewing all critical feeders annually.

Conclusion

Professional electrical cable sizing requires a structured approach combining calculations, standards, derating analysis and field experience. By applying the steps demonstrated in this tutorial — with clear equations, validated assumptions and real-world examples — engineers can ensure installations are safe, compliant and optimized for long-term performance.